26 Reconnection/Adjustments TP-6335 9/04
8.1 Four-Lead Reconnection
The following drawings illustrate the reconnection of
four-lead generator sets. In all cases, conform to the
National Electrical Code (NEC).
NOTICE
Voltage reconnection. Affix a notice to the generator set after
reconnecting the set to a voltage different from the voltage on
the nameplate. Order voltage reconnection decal 246242
from an authorized service distributor/dealer.
100--120-Volt Configurations
If the installation requires a factory two-pole circuit
breaker, do not connect the load-side terminals of the
circuit breaker. See Figure 8-1. If the installation
requires a 100--120-volt, 2-wire system, use a
single-pole circuit breaker. See Figure 8-2. When
connecting stator phase leads together, size the output
lead (L1) to handle the amperage. Use a jumper lead on
the line side of the circuit breaker to balance the load of
the generator set.
GRD.
L1
L2
4321
L0 (Neutral)
L0
Ground
Load
Side
Line
Side
Two-Pole
Circuit
Breaker
Jumper
Lead
Figure 8-1 100--120-Volt, 3-Wire Configuration
100--120/200--240-Volt Configurations
The 100--120/200--240-volt configuration does not use
a jumper lead. If the unit was originally wired for straight
100--120 volt, 3 wire, remove the jumper lead (see
Figure 8-1 for location). Select a two-pole circuit
breaker. Application of two single-pole circuit breakers
does not conform to NEC requirements for supplying a
200--240 volt load—even if the breakers are
mechanically attached. Leads L1 and L2 are for
different phases—never connect them.
4321
Stator Leads
L0
GRD.
L1
L0 (Neutral)
Line
Side
Single-Pole
Circuit
Breaker
Ground
Load
Side
60 Hz
L0--L1 100--120 Volt
L0--L2 100--120 Volt
Figure 8-2 100--120-Volt, 2-Wire Configuration
4321
Stator Leads
L0
GRD.
L2
L1
L0 (Neutral)
Line
Side
Factory
Two-Pole
Circuit
Breaker
Ground
Load
Side
100--120/200--240 Volt,
3 Wire
60 Hz
L0--L1 100--120 Volt
L0--L2 100--120 Volt
L1--L2 200--240 Volt
Figure 8-3 100--120/200--240-Volt,
3-Wire Configuration