TP-5700 7/9322 Section 5 Exhaust System
5.1 Flexible Section
A section of flexible exhaust line should be installed
within 2 feet (51 mm) of the engine exhaust outlet. This
limits the stress on the engine exhaust manifold or
turbocharger resulting from engine motion on its
vibration mounts and temperature-induced changes in
pipe dimensions. Never allow the engine manifold or
turbocharger to support the silencer or exhaust piping
weight. The flexible section should be at least 12 inches
(305 mm) long.
Where threaded flexible exhaust connectors are used, a
6-8 inch (152-203 mm) length of pipe should separate
them from the exhaust manifold. This will serve to
reduce the temperature of the flexible connection and
extend its life. It also makes it easier to remove the
flexible section, if necessary, without putting excessive
strain on the engine manifold.
The flexible section should not be bent or used to make
up for misalignment between the engine exhaust and
the exhaust piping. Since typical exhaust temperatures
range from 800°F (427°C) to over 1200°F (649°C) for
some engines, seamless stainless steel should be used
for the flexible section.
5.2 Condensation Trap
A Y- or tee-type condensation trap with a drain plug or
petcock should be installed between the engine and
exhaust silencer as shown in Figure 5-3. This will
prevent condensed moisture in the engine exhaust from
draining into the engine when it is shut down. The trap
should be drained of collected moisture periodically.
1
TP-5700-5
1. Condensation trap
Figure 5-3 Condensation Trap
5.3 Piping
Exhaust piping should conform to all applicable codes.
In general, exhaust temperatures will be less than
1000°F (538°C) measured at the engine exhaust outlet,
except for infrequent brief periods, and standards for
low heat appliances will apply. For units with exhaust
temperatures below 1000°F (538°C), exhaust piping
should be routed a minimum of 18 inches (457 mm) from
any combustible materials. If exhaust temperatures will
exceed 1000°F (538°C), the minimum distance should
be 36 inches (914 mm).
The heat rejected by exhaust piping, and consequently
the amount of ventilating air required, can be
substantially reduced by insulating exhaust piping with
suitable high-temperature insulation. Exhaust
temperatures are given on each generator model’s
specification sheet.
Placement of exhaust silencer and piping should
consider location of combustible materials. If location of
exhaust cannot avoid these concerns, use a regular
maintenance routine to remove combustible materials.
Combustible materials include building materials as well
as natural surroundings. Keep dry field grass, foliage,
and combustible landscaping material whether or not
seasonal a s afe distance from the exhaust system.