TP-5700 7/93 23Section 5 Exhaust System
5.4 Double-Sleeve Thimbles
If the exhaust pipe should need to pass through a wall or
roof, an exhaust thimble must be used to prevent
exhaust pipe heat from being transmitted to the
combustible material. Construction details for a typical
double-sleeve thimble to be used where exhaust piping
passes through a combustible roof or wall are shown in
Figure 5-4. They are usually fabricated at a local sheet
metal shop to the specifications furnished by the
installation engineer.
The thimbles should be constructed so that they extend
at least 10 inches (25.40 cm) both ways from the surface
of the wall or roof. Holes are provided at both ends to
allow cooling air to circulate through the thimble. If
screening is used on the outer end to keep birds,
rodents, etc., from entering the thimble, make sure that
the mesh is large enough so that it doesn’t impair air
circulation through the thimble. If the exhaust pipe must
exit through a roof, a rain shield must be included above
the thimble as shown in Figure 5-4. The rain cap as
shown on the end of the exhaust pipe is recommended
only in areas not subject to freezing temperatures. In an
area where freezing is common, extend the exhaust
piping well beyond the roof and use a gradual “U” bend
at the end to direct the exhaust outlet downward which
will keep rain, snow, etc., out of the pipe. The outlet of the
pipe should be far enough from the roof to prevent
ignition of the roof material from hot exhaust.
5
8
1
2
3
4
9
7
6
10
11
15
12
13
14
TP-5700-5
6
1. Rain cap (or gradual U bend)
2. Rain shield
3. 10 in. (254 mm) minimum
4. 1 in. (25 mm) minimum
5. Exhaust pipe
6. Ventilation holes at both ends
7. 10 in. (254 mm) minimum
8. 1 in. (25 mm) minimum
9. Flashing
10. Inner sleeve
11. Outer sleeve
12. Thimble outer diameter
13. 10 in. (254 mm) minimum outside
14. 10 in. (254 mm) minimum inside
15. Exhaust pipe diameter
Figure 5-4 Double-Sleeved Thimbles and Rain Cap