Commercial Mobile Generator SetsModel:10ERG13ERG15ERGTP-6335 9/04Installation
VI Safety Precautions and InstructionsTP-6335 9/04Notes
1IntroductionTP-6335 9/04Section 1 IntroductionAll information in this publication represents dataavailable at the time of print. Kohler Co. reserves
2Introduction TP-6335 9/04Notes
TP-6335 9/04 Location and Mounting 3Section 2 Location and Mounting2.1 General ConsiderationsConsider the following items concerning the generatorset
4 Location and Mounting TP-6335 9/04Notes
TP-6335 9/04 Cooling System 5Section 3 Cooling System3.1 Air RequirementsAir flow around the generator set is necessary foradequate cooling. See the c
6 Cooling System TP-6335 9/04Notes
7TP-6335 9/04 Exhaust System 7Section 4 Exhaust SystemCarbon monoxide.Can cause severe nausea, fainting,or death.The exhaust system must beleakproof a
TP-6335 9/048 Exhaust System4.1 PlanningCarefully plan the generator exhaust system to ensure asafe, quiet installation. Verify that the installationc
TP-6335 9/04 Fuel System 9Section 5 Fuel SystemExplosive fuel vapors.Can cause severe injury or death.Use extreme care when handling,storing, and usin
TP-6335 9/0410 Fuel System5.1.1 Fuel LinesNote: Keep fuel lines away from the exhaust system.Routing fuel lines. Take care when routing the fuel linef
TP-6335 9/04 Fuel System 115.4 Fuel Pump Lift and FuelConsumptionSee Figure 5-3 for the fuel pump lift capability. Consultthe current generator set sp
TP-6335 9/0412 Fuel SystemNotes
TP-6335 9/04 Electrical System 13Section 6 Electrical SystemHazardous voltage.Can cause severe injury or death.Operate the generator set only whenall
14 Electrical System TP-6335 9/04Note: Transfer switch. Use a triple-pole, double-throwtransfer switch rated for the calculated load of thevehicle to
TP-6335 9/04 Electrical System 156.3 Circuit ProtectionThe AC circuit breaker protects the generator set fromextreme overload. The AC circuit breaker
16 Electrical System TP-6335 9/046.3.2 Circuit Breaker InstallationNote: Wire material. Use stranded copper for allwiring. Use wire gauges and insulat
TP-6335 9/04 Electrical System 176.4 ADC 2100 Continuous PowerMode JumperA jumper on connector P7 on the back of the controllercauses the controller t
18 Electrical System TP-6335 9/046.5 Battery and ConnectionsSulfuric acid in batteries.Can cause severe injury or death.Use protective goggles and clo
TP-6335 9/04 Electrical System 19-- +BatteryPositiveVehicleFrame12-VoltBatteryUsing the Same Batteryas the Vehicle EngineNBattery Negativeto Vehicle F
Table of ContentsSafety Precautions and Instructions I...Section 1 Introduction 1...
20 Electrical System TP-6335 9/04Notes
Installation Drawing 21TP-6335 9/04Section 7 Installation DrawingADV-6816A-AFigure 7-1 Dimension Drawing, Gasoline Fuel System
TP-6335 9/0422 Installation DrawingADV-6816B-AFigure 7-2 Dimension Drawing, LP Fuel System
Installation Drawing 23TP-6335 9/04ADV-6816C-AFigure 7-3 Dimension Drawing, Floor Template
TP-6335 9/0424 Installation DrawingNotes
TP-6335 9/04 Reconnection/Adjustments 25Section 8 Reconnection/AdjustmentsAccidental starting.Can cause severe injury or death.Disconnect the battery
26 Reconnection/Adjustments TP-6335 9/048.1 Four-Lead ReconnectionThe following drawings illustrate the reconnection offour-lead generator sets. In al
TP-6335 9/04 Reconnection/Adjustments 27200--240-Volt ConfigurationsThe 200--240-volt configuration does not use a jumperlead. If the unit was origina
28 Reconnection/Adjustments TP-6335 9/048.2 Advanced Digital Control(ADC 2100)The model 10/13/15ERG generator sets use theADC 2100. The ADC 2100 uses
TP-6335 9/04 Reconnection/Adjustments 298.2.3 Adjusting the Voltage, Gain, andVolts/HzAfter setting the system voltage, check the outputvoltage and ad
Notes
30 Reconnection/Adjustments TP-6335 9/04TP6196Move the generator set master switch to the RUN position. The generator setengine starts and the control
TP-6335 9/04 Reconnection/Adjustments 31Display:*Continued from Figure 8-6:* x in the examples above denotes any number from 0 to 9. The actual values
32 Reconnection/Adjustments TP-6335 9/048.2.5 Controller ConfigurationThe controller configuration for each generator model isset at the factory and s
TP-6335 9/04 Reconnection/Adjustments 33Parameter Setting DefinitionUnit’s system voltageand frequencyUu01 Single phase, 60 Hz, 120/240 VACUnit config
34 Reconnection/Adjustments TP-6335 9/04Wait about 5 seconds until the display shows theprogram version number. (The number may bedifferent than the o
TP-6335 9/04 Reconnection/Adjustments 35orTo set the engine data input type.To enter battery voltage selection mode.orTo toggle between 12 and 24 VDC.
36 Reconnection/Adjustments TP-6335 9/04Notes
TP-6335 9/04 Appendix A-1Appendix A Generator Selection and Wattage RequirementsGeneral Wattage RequirementsConsider the total wattage requirements (l
TP-6335 9/04A-2 AppendixAppendix B AbbreviationsThe following list contains abbreviations that may appear in this publication.A, amp ampereABDC after
TP-6335 9/04 Appendix A-3kg kilogramkg/cm2kilograms per squarecentimeterkgm kilogram-meterkg/m3kilograms per cubic meterkHz kilohertzkJ kilojoulekm ki
Safety Precautions and Instructions ITP-6335 9/04Safety Precautions and InstructionsIMPORTANT SAFETYINSTRUCTIONS. Electromechanicalequipment, includin
E 2004 by Kohler Co. All rights reserved.TP-6335 9/04KOHLER CO. Kohler, Wisconsin 53044Phone 920-565-3381, Fax 920-459-1646For the nearest sales/servi
II Safety Precautions and InstructionsTP-6335 9/04Battery short circuits. Explosioncan cause severe injury or death.Short circuits can cause bodily in