Important Product Information (cont.)
Electrical Requirements
The installation must have two Class A Ground-Fault Circuit-Interrupters (GFCI’s) or Earth-Leakage
Circuit-Breakers (ELCB’s). The GFCI/ELCB protects against line-to-ground shock hazard. Use a 208-240 V, 20
A, 50/60 Hz dedicated service for the pump controls. Use a separate 208-240 V, 20 A, 50/60 Hz dedicated
service for the heater.
An equipment grounding terminal is provided in the field wiring compartment. To reduce the risk of
electrical shock, this terminal must be connected to the grounding means provided in the electrical supply
panel with a conductor equivalent in size to the circuit conductors supplying this equipment.
Install this unit in accordance with the Canadian Electric code, Part I.
Kohler Co. 3 1054216-2-A