  • TROUBLESHOOTING
  • BOOKMARKS
  • Rated. / 5. Based on customer reviews
Page view 135
8.20
Section 8
Electrical System and Components
6. Press the ‘‘TEST’’ button until a ‘‘click’’ is heard
and then release. See Figure 8-27. Momentarily
one of the four status lights will illuminate
indicating the partial condition of the part.
a. If the ‘‘OK’’ (green) light comes on, disconnect
the tester black lead attached to one AC
terminal and reconnect it to the other AC
terminal. Repeat the test. If the ‘‘OK’’ (green)
light comes on again, the part is good and
may be used.
b. If any other light is displayed* in either of the
tests, the rectifier-regulator is faulty and
should not be used.
*NOTE: A flashing ‘‘LOW’’ light can also occur as a
result of an inadequate ground lead
connection. Make certain the connection
location is clean and the clamp is secure.
25 Amp Rectifier-Regulators (Original Style)
1. Connect the squared single end of the tandem
lead adapter to the B+ (center/red) lead of the
rectifier-regulator being tested. See Figure 8-30.
Figure 8-30.
2. Connect the ground lead of tester (with spring
clamp), to the housing of rectifier-regulator.
3. Connect the red lead and one of the black leads
from the tester to the pair of terminals on opposite
end of adapter lead (connections are not location
specific.).
4. Connect the remaining black lead from tester to one
of the black AC (outside) leads from rectifier-
regulator. See Figure 8-31.
Figure 8-31.
5. Plug the tester into the proper AC outlet/power
supply for tester being used. Turn on the power
switch. The ‘‘POWER’’ light should be
illuminated and one of the four status lights may
be on as well. See Figure 8-26. This does not
represent the condition of the part.
6. Press the ‘‘TEST’’ button until a “click” is heard
and then release. See Figure 8-27. Momentarily
one of the four lights will relight indicating the
partial condition of the part.
a. If the “OK” (green) light comes on, disconnect
the tester black lead attached to the AC lead,
reconnect it to the opposite side AC lead, and
repeat the test. If the “OK” light (green) again
comes on, the part is good and may be used.
b. If any other light is displayed* in either of the
tests, the rectifier-regulator is faulty and
should not be used.
*NOTE: A flashing “LOW” light can also occur as a
result of an inadequate ground lead
connection. Make certain connection location
is clean and clamp is secure.
4 Amp Unregulated Rectifiers
1. Connect the tester ground lead (with spring
clamp), to the body of the rectifier being tested.
2. Connect the red tester lead to the B+ (center)
terminal of the rectifier and the two black tester
leads to the two AC (outside) terminals. See
Figure 8-32.