Important Product Information (cont.)
Connections and Service Access
NOTICE: Provide unrestricted service access to the pump and heater. Provide unrestricted service access
to the pump, in-line heater, adjustable feet, and control box. You must construct an access panel to provide
sufficient clearance for servicing the pump, in-line heater, and control box. The access panel must be
located immediately next to the pump and in-line heater. Study the roughing-in information.
Electrical Requirements
The installation must have two Class A Ground-Fault Circuit-Interrupters (GFCI’s) or Earth-Leakage
Circuit-Breaker (ELCB’s). The GFCI/ELCB protects against line-to-ground shock hazard. Use a 240 V, 20 A,
50/60 Hz dedicated service for the pump controls. Use a separate 240 V, 20 A, 50/60 Hz dedicated service
for the heater.
An equipment grounding terminal is provided in the field wiring compartment. To reduce the risk of
electrical shock, this terminal must be connected to the grounding means provided in the electrical supply
panel with a conductor equivalent in size to the circuit conductors supplying this equipment.
Install this unit in accordance with the Canadian Electric code, Part I.